Multicore 90°C Armoured Thermosetting Insulated Cables (COPPER CONDUCTORS)
Tables Apply to: H6942XL, H6943XL, H6944XL, H6945XL, Tuff Sheath,
CURRENT-CARRYING CAPACITY (amperes)
Conductor Cross Sectional Area | Reference Method C (clipped direct) | Reference Method E (in free air or on a perforated cable tray etc, horizontal or vertical) | Reference Method D (direct in ground or in ducting in ground, in or around buildings) | |||
|---|---|---|---|---|---|---|
1 two-core cable single-phase a.c. or d.c. | 1 three-or 1 four-core cable, three-phase a.c. | 1 two-core cable single-phase a.c. or d.c. | 1 three-or 1 four-core cable, three-phase a.c. | 1 two-core cable single-phase a.c. or d.c. | 1 three-or 1 four-core cable, three-phase a.c. | |
1 | 2 | 3 | 4 | 5 | 6 | 7 |
(mm2) | (A) | (A) | (A) | (A) | (A) | (A) |
1.5 | 27 | 23 | 29 | 25 | 25 | 21 |
2.5 | 36 | 31 | 39 | 33 | 33 | 28 |
4 | 49 | 42 | 52 | 44 | 46 | 36 |
6 | 62 | 53 | 66 | 56 | 53 | 44 |
10 | 85 | 73 | 90 | 78 | 71 | 58 |
16 | 110 | 94 | 115 | 99 | 91 | 75 |
25 | 146 | 124 | 152 | 131 | 116 | 96 |
35 | 180 | 154 | 188 | 162 | 139 | 115 |
50 | 219 | 187 | 228 | 197 | 164 | 135 |
70 | 279 | 238 | 291 | 251 | 203 | 167 |
95 | 338 | 289 | 354 | 304 | 239 | 197 |
120 | 392 | 335 | 410 | 353 | 271 | 223 |
150 | 451 | 386 | 472 | 406 | 306 | 251 |
185 | 515 | 441 | 539 | 463 | 343 | 281 |
240 | 607 | 520 | 636 | 546 | 395 | 324 |
300 | 698 | 599 | 732 | 628 | 446 | 365 |
400 | 787 | 673 | 847 | 728 | - | - |
NOTES :
- Where a conductor operates at a temperature exceeding 70°C it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see Regulation 512.1.2)
- Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70°C, the current ratings given in the equivalent table for 70°C thermoplastic insulated cables (Table 4D4A) must be used (see also Regulation 523.1)
VOLTAGE DROP (per ampere per metre)
Conductor Cross Sectional Area | Two-core cable d.c. | Two-core cable, single-phase a.c. | Three- or four-core cable, three-phase a.c. | ||||
|---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | ||||
(mm2) | (mV/A/m) | (mV/A/m) | (mV/A/m) | ||||
1.5 | 31 | 31 | 27 | ||||
2.5 | 19 | 19 | 16 | ||||
4 | 12 | 12 | 10 | ||||
6 | 7.9 | 7.9 | 6.8 | ||||
10 | 4.7 | 4.7 | 4 | ||||
16 | 2.9 | 2.9 | 2.5 | ||||
r | x | z | r | x | z | ||
25 | 1.85 | 1.85 | 0.16 | 1.9 | 1.6 | 0.14 | 1.65 |
35 | 1.35 | 1.35 | 0.155 | 1.35 | 1.15 | 0.135 | 1.15 |
50 | 0.98 | 0.99 | 0.155 | 1 | 0.86 | 0.135 | 0.87 |
70 | 0.67 | 0.67 | 0.15 | 0.69 | 0.59 | 0.13 | 0.6 |
95 | 0.49 | 0.5 | 0.15 | 0.52 | 0.43 | 0.13 | 0.45 |
120 | 0.39 | 0.4 | 0.145 | 0.42 | 0.34 | 0.13 | 0.37 |
150 | 0.31 | 0.32 | 0.145 | 0.35 | 0.28 | 0.125 | 0.3 |
185 | 0.25 | 0.26 | 0.145 | 0.29 | 0.22 | 0.125 | 0.26 |
240 | 0.195 | 0.2 | 0.14 | 0.24 | 0.175 | 0.125 | 0.21 |
300 | 0.155 | 0.16 | 0.14 | 0.21 | 0.14 | 0.12 | 0.185 |
400 | 0.12 | 0.13 | 0.14 | 0.19 | 0.115 | 0.12 | 0.165 |