EV-ULTRA with 4 pair data

EV-ULTRA 3 CORE 4.0 SQMM SWA POWER + CAT5 CABLE

Manufactured in the UK This cable is designed for use in the installation of electric vehicle charge points. The cable incorporates power conductors and an enhanced Cat 5 screened data cable, encapsulated in a double sheathed design for extra protection. Whilst designed for use in electric vehicle charge points, the cable is also suitable for other installations where power and data is required. These cables are designed to be installed in air, clipped to surface, on cable tray/ladder work and embedded in concrete. The cables can be laid direct in the ground providing that suitable mechanical protection is in place.

SKU: EV-ULTRA3C4.0CAT5SWA
Reference: 10535493
Product Group: EV-ULTRA Cat5e
Supplier: Doncaster Cables

Certifications & Standards

Certification Logo Certification Logo Certification Logo

Quick Facts


SKU
EV-ULTRA3C4.0CAT5SWA
Reference
10535493
Product Group
EV-ULTRA Cat5e
Specifications
29

Technical Specifications

Weight
568.65
Unit
1000
Number of conductors
3 + DATA
Conductor Size
4
Construction
Plain Annealed Copper / Thermosetting XLPE / CarbonTek® /Galvanised steel wire armour / CarbonTek
Standard
BASEC CAD045 Approved
Conductor
Plain Annealed Copper Class 2 Stranded to BS EN 60228
Insulation
Thermosetting XLPE Type GP8 to BS 7655-1.3
Bedding
CarbonTek®
Armouring
Galvanised steel wire armour
Sheathing
CarbonTek®
Minimum Operating Temperature
-15°C
Maximum Operating Temperature
90°C
Minimum Bending Radius
8 x diameter
Reel Dimensions (mm)
1000x1000x600
Core Colours
Green/Yellow, Blue, and Brown
Nominal Stranding of Conductor (mm)
7/0.85
Nominal Radial Thickness of Insulation (mm)
0.7
Nominal Radial Thickness of Sheath (mm)
1
Nominal Overall Diameter of Bedding (mm)
12.5
Approximate Weight (kg/km)
510
Galv. Steel Wire Armour
0.9mm
Maximum Current Rating (A)
45
Voltage drop (mV/A/m)
12
Recommendations
Running data and power in a single cable is a concern for many electricians, with most believing that segregation of power (Band II) and data (Band I) is always required. It is however already common to find power and data inside one cable in many existing applications, an example is DALI networks which incorporate data within a 5 core power cable. It is recommended that the screening of the data cable is terminated to earth.
Voltage Band I
is defined as levels of voltage which are too low to provide serious electric shocks; effectively this limits the band to extra-low voltage (ELV), including telecommunications, signalling, bell, control and alarm circuits.
Voltage Band II
is defined as all voltages which are used in electrical installations not included in Band I. This means that all 230V supplies are included in Band II.
Proximity of Electrical services (extract from 528.1)
- Except where one of the following methods is adopted, neither a Band I nor a Band II circuit shall be contained in the same wiring system as a circuit of nominal voltage exceeding that of low voltage, and a Band I circuit shall not be contained in the same wiring system as a Band II circuit. (i) - Every cable or conductor is insulated for the highest voltage present. EV-Ultra® consists of power conductors and data cables that are rated to the same nominal voltage – therefore segregation of power and data is not required.
Proximity of communications cables
- Special considerations of electrical interference, both electromagnetic and electrostatic, may apply to telecommunication circuits, data transfer circuits and the like. EV-Ultra® has been designed with these considerations in mind, it incorporates screened, twisted pair data cables and is also constructed with a lay length that reduces interference. Laboratory and on-site installation tests have also been conducted and no interference or degredation of signal was recorded.