H FIRESURE PLUS ENHANCED 4 CORE

H FIRESURE PLUS ENHANCED 3 CORE 1.5 WHITE 100 M

Our Firesure Plus cable has at least twice as many copper tapes than any other leading Fire Performance Cable; some other enhanced fire performance cables even opt to use an aluminium tape (usually seen on standard fire performance cables). The Firesure Plus design also incorporates a glass fibre tape which covers the inner conductors. These additional protections improve the fire performance and general characteristics of our cable. The Doncaster Cables Firesure Plus design offers numerous advantages in comparison to some other suppliers who opt for a ‘longitudinally applied tape’ design. These longitudinal designs mean that the metallic tape required is simply folded along the inner conductors with a minimum 1mm tape overlap. In comparison to this, the Firesure Plus design consists of 2 ‘helically’ applied copper tapes. This helically applied tape design means that both tapes are continuously wrapped around the conductors with a minimum tape overlap of 20%. This increased overlap allows for the following key performance benefits. The following benefits are further amplified through Firesure Plus cable as there are two metallic tapes as opposed to the minimum British Standard requirement of a single tape. These cables are suitable for both indoor and outdoor applications in suitably protected environments and is particularly appropriate for direct burial in plaster, clipped directly to surface, tray and other installations requiring a dressable product.

SKU: HFSP3C1.5W100
Reference: 10536446
Product Group: HFSP
Supplier: Doncaster Cables

Certifications & Standards

Certification Logo Certification Logo Certification Logo

Quick Facts


SKU
HFSP3C1.5W100
Reference
10536446
Product Group
HFSP
Specifications
35

Technical Specifications

Weight
164.8
Unit
1000
Number of conductors
3
Conductor Size
1.5
Construction
Plain Annealed Copper Conductors / Silicone Rubber Insulated / Glass Fibre Tape / Plain Annealed Copper Conductors / Silicone Rubber Insulated / Glass Fibre Tape / Tinned Copper Circuit Protective Conductor / Double Layer of Copper/Polyester Tapes / Thermoplastic Low Smoke Non-Halogen (LSNH) Sheath. 300/500V
Standard
BS 7629-1
Table / Clause
Table 1
Conductor
Plain Annealed Copper Class 1 or 2 to BS EN 60228
Insulation
Silicone Rubber Type EI2 to BS EN 50363-1
Sheathing
Thermoplastic LSNH Type LTS 3 to BS 7655-6.1
Voltage Rating
300/500V
Minimum Operating Temperature
-15°C
Maximum Operating Temperature
70°C
Minimum Bending Radius
6 x diameter
Colour
White
Reel Dimensions (mm)
375x375x300
Core Colours
Brown, Black, and Grey
Current Ratings
For current ratings refer to table 4D2A of BS7671 IEE Wiring Regulations
Current Rating (In Air (A))
Table 4D2A of BS7671 IEE Wiring Regulations Reference Method E
Nominal Stranding of Conductor (mm)
1/1.38
Nominal Stranding of CPC (mm)
1/1.38
Nominal Radial Thickness of Insulation (mm)
0.7
Nominal Radial Thickness of Sheath (mm)
0.9
Approximate Overall Diameter (mm)
10
Approximate Weight (kg/km)
TBA
Recommended Clip (DC)
37
Maximum Horizontal Clipping Distance
300
Maximum Vertical Clipping Distance
400
Cable Types
FIRE PERFORMANCE (ENHANCED) MULTICORE AND EARTH
Meterage of each Component
100 Metres
Conductor Class to BS EN 60228
Class 1
Bullet1
Manufactured in the UK
Bullet2
Manufactured with 100% renewable energy
Bullet3
Uses materials and manufacturing techniques designed to make the electricians life easier
Bullet4
LPCB Approved