AUXILIARY SWA LSNH

7 CORE 2.5 STRANDED XLPE/LSNH/SWA/LSNH

These cables are designed to be used in installations where smoke and acid gas emission would pose a major hazard in the event of a fire.

Auxiliary Steel Wire Armoured cables are predominantly used for industrial wiring and signalling.

They are designed to be used in industrial areas, areas with higher risk of mechanical stress/damage, in and around buildings and other similar environments.

These cables are designed to be installed in air, clipped to surface, on cable tray/ladder work, embedded in concrete and buried direct or in ducting underground.

  • Multicore Loading
  • In practice, the majority of cores in a multicore control cable of 7 cores and above carry only small or intermittent current and a current rating based on the assumption that all cores are equally loaded is quite unrealistic. In most cases only two cores, the live and neutral feed cores are likely to approach the maximum permitted loading. The current rating for twin core cable can therefore be used in these cables.
  • Where more than two cores are known to carry an appreciable current, the multiplying factors applicable to the two core ratings are given below. The normal current rating for twin cable may also be used in cases where the number of cores carrying appreciable current does not exceed the square root of the total number of cores in the cable.

Variation Details

Donc 7C2.5LSNH 7 Core Cable LSNH 2.5mm
SKU: 7C2.5LSNH
Product Group: LSNH SWA
Supplier: Doncaster Cables

Quick Facts


SKU
7C2.5LSNH
Product Group
LSNH SWA
Specifications
36

Technical Specifications

Weight
497.25
Unit
1000
Number of conductors
7
Conductor Size
2.5
Construction
Plain Annealed Copper Conductor / XLPE Insulated / LSNH Bedded / Galvanised Steel Wire Armour / LSNH Sheathed. 600/1000V
Standard
BS 6724
Table / Clause
Table 18
Conductor
Plain Annealed Copper Class 2 Stranded to BSEN 60228
Insulation
Thermosetting XLPE Type GP8 to BS 7655-1.3
Armouring
Yes
Sheathing
LSNH Type LTS1 to BS 7655-6.1
Voltage Rating
600/1000V
Minimum Operating Temperature
-15°C
Maximum Operating Temperature
90°C
Minimum Bending Radius
8 x diameter
Reel Dimensions (mm)
1000x1000x600
Core Colours
White, Numbered Black
Current Ratings
For current ratings refer to table 4E4A of BS7671 IET Wiring Regulations.
Nominal Stranding of Conductor (mm)
7/0.67
Nominal Radial Thickness of Insulation (mm)
0.7
Nominal Radial Thickness of Bedding (mm)
0.8
Approximate Weight (kg/km)
618
Recommended Gland Size
20
Weight
497.25
Unit
1000
Conductor Size
2.5
Construction
Plain Annealed Copper Conductor / XLPE Insulated / LSNH Bedded / Galvanised Steel Wire Armour / LSNH Sheathed. 600/1000V
Standard
BS 6724
Conductor
Plain Annealed Copper Class 2 Stranded to BSEN 60228
Insulation
Thermosetting XLPE Type GP8 to BS 7655-1.3
Armouring
Yes
Voltage Rating
600/1000V
Minimum Operating Temperature
-15°C
Maximum Operating Temperature
90°C
Minimum Bending Radius
8 x diameter
Core Colours
White, Numbered Black