AUXILIARY SWA LSNH

These cables are designed to be used in installations where smoke and acid gas emission would pose a major hazard in the event of a fire.

Auxiliary Steel Wire Armoured cables are predominantly used for industrial wiring and signalling.

They are designed to be used in industrial areas, areas with higher risk of mechanical stress/damage, in and around buildings and other similar environments.

These cables are designed to be installed in air, clipped to surface, on cable tray/ladder work, embedded in concrete and buried direct or in ducting underground.

  • Multicore Loading
  • In practice, the majority of cores in a multicore control cable of 7 cores and above carry only small or intermittent current and a current rating based on the assumption that all cores are equally loaded is quite unrealistic. In most cases only two cores, the live and neutral feed cores are likely to approach the maximum permitted loading. The current rating for twin core cable can therefore be used in these cables.
  • Where more than two cores are known to carry an appreciable current, the multiplying factors applicable to the two core ratings are given below. The normal current rating for twin cable may also be used in cases where the number of cores carrying appreciable current does not exceed the square root of the total number of cores in the cable.
AUXILIARY SWA LSNH

Available Variations


Name Core Colours Number of conductors Conductor Size Standard Current Ratings Weight Voltage Rating Reel Dimensions (mm) Details
7 CORE 1.5 STRANDED XLPE/LSNH/SWA/LSNH White, Numbered Black 7 1.5 BS 6724 For current ratings refer to table 4E4A of BS7671 IET Wiring Regulations. 368.77 600/1000V 1000x1000x600 View
7 CORE 2.5 STRANDED XLPE/LSNH/SWA/LSNH White, Numbered Black 7 2.5 BS 6724 For current ratings refer to table 4E4A of BS7671 IET Wiring Regulations. 497.25 600/1000V 1000x1000x600 View
12CORE 1.5 STRANDED XLPE/LSNH/SWA/LSNH White, Numbered Black 12 1.5 BS 6724 For current ratings refer to table 4E4A of BS7671 IET Wiring Regulations. 676.2 600/1000V View
12CORE 2.5 STRANDED XLPE/LSNH/SWA/LSNH White, Numbered Black 12 2.5 BS 6724 For current ratings refer to table 4E4A of BS7671 IET Wiring Regulations. 913.42 600/1000V View

Dimensional Details

Product Code Number and Nominal Cross Sectional Area of Conductors (mm²) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of bedding (mm) Approximate Overall Diameter (mm) Approximate Weight (kg/km) Reccomended Gland Size
7C1.5LSNH 7 x 1.5 7/0.53 0.6 0.8 15.2 506 20S
7C2.5LSNH 7 x 2.5 7/0.67 0.7 0.8 17.1 618 20
7C4.0LSNH 7 x 4.0 7/0.85 0.7 0.8 19.7 904 25
7C6.0LSNH * 7 x 6.0 7/1.04 0.7 0.8 21.3 1110 25
7C710LSNH * 7 x 10.0 7/1.35 0.7 0.8 25.6 1720 25
12C1.5LSNH 12 x 1.5 7/0.53 0.6 0.8 19.4 854 25
12C2.5LSNH 12 x 2.5 7/0.67 0.7 0.8 22.4 1080 25
12C4.0LSNH 12 x 4.0 7/0.85 0.7 1.0 25.7 1550 32
19C1.5LSNH 19 x 1.5 7/0.53 0.6 0.8 22.2 1120 25
19C2.5LSNH 19 x 2.5 7/0.67 0.7 1.0 26.6 1570 25
*Manufactured generally to BS6724, not BASEC approved
Weight and dimensional information is provided as an approximate guide only.

Core Details

Number of loaded cores 3 4 5 6 7 10 12 14
Multiplying factor 0.87 0.78 0.72 0.67 0.63 0.56 0.53 0.51
Number of loaded cores 19 24 27 30 37 44 46 48
Multiplying factor 0.45 0.42 0.4 0.39 0.36 0.34 0.33 0.33